Sterling Gas Heater GF 150 User Manual

(S) DSTBIM-3  
J30-06935  
INSTALLATION INSTRUCTIONS AND PARTS LIST  
TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS  
ATTENTION: READ THIS MANUAL AND ALL LABELS ATTACHED TO THE UNIT CAREFULLY BEFORE  
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE UNITS! CHECK UNIT DATA PLATE FOR TYPE OF GAS  
AND ELECTRICAL SPECIFICATIONS AND MAKE CERTAIN THAT THESE AGREE WITH THOSE AT THE POINT OF  
INSTALLATION. RECORD THE UNIT MODEL AND SERIAL No.(s) IN THE SPACE PROVIDED. RETAIN FOR FUTURE  
REFERENCE.  
Model No.  
Serial No.  
FORYOUR SAFETY  
The use and storage of gasoline or other flammable vapors and liquids in open containers in  
the vicinity of this appliance is hazardous.  
FORYOUR SAFETY  
If you smell gas:  
1. Open windows.  
2. Don't touch electrical switches.  
3. Extinguish any open flame.  
4.Immediately contact your gas supplier.  
Improper installation, adjustment, alteration, service, or maintenance  
can cause property damage, injury, or death. Read the installation, operating, and  
maintenance instruction thoroughly before installing or servicing this equipment.  
APPROVED FOR USE IN CALIFORNIA  
Install, operate, and maintain unit in accordance with the manufacturer's  
instructions to avoid exposure to fuel substances, or substances from incomplete  
combustion, which can cause death or serious illness. The state of California  
has determined that these substances may cause cancer, birth defects, or other  
reproductive harm.  
INSTALLER'S RESPONSIBILITY  
Installer Please Note: This equipment has been test fired and inspected. It has been  
shipped free from defects from our factory. However, shipment and installation  
problems such as loose wires, leaks, or loose fasteners may occur. It is the installer's  
responsibility to inspect and correct any problem that may be found.  
RECEIVING INSTRUCTIONS  
Inspect shipment immediately when  
received to determine if any damage  
has occurred to the unit during  
shipment. After the unit has been  
uncrated, check for any visible  
damage to the unit. If any damage  
is found, the consignee should sign  
the bill of lading indicating such  
damage and immediately file claim  
for damage with the transportation  
company.  
HVAC PRODUCTS  
260 NORTH ELM ST., WESTFIELD, MA 01085  
TEL: (413) 564-5540 FAX: (413) 562-5311  
MODELS: TF-100, 125, 150, 175, 200, 250,  
300, 350, 400 GF-150, 250, 400  
Please utilize this toll free number to contact your local  
representative 800-490-2290.  
03/07  
 
GENERAL SAFETY INFORMATION  
Failure to comply with the general  
Do not attempt to convert the  
heater for use with a fuel other than the one  
intended. Such conversion is dangerous, as it  
will create the risks previously listed.  
safety information may result in extensive  
property damage, severe personal injury, or  
death.  
Make certain that the power source conforms to the  
electrical requirements of the heater.  
This product must be installed by  
a licensed plumber or gas fitter when installed  
within the Commonwealth of Massachusetts.  
Do not depend upon a thermostat  
or other switch as sole means of disconnecting  
power when installing or servicing heater. Always  
disconnect power at main circuit breaker as  
described above. Failure to do so could result in  
fatal electric shock.  
Installation must be made in accordance with local  
codes, or in absence of local codes, with the latest  
edition of the ANSI Standard Z223.1 (N.F.P.A. No. 54)  
National Fuel Gas Code. All of the ANSI and NFPA  
Standards referred to in these installation instructions  
are those that were applicable at the time the design  
of this appliance was certified. The ANSI Standards  
are available from CSA Information Services, 1-800-  
463-6727. The NFPA Standards are available from the  
National Fire Protection Association, Batterymarch Park,  
Quincy, MA 02269. These unit heaters are designed for  
use in airplane hangars when installed in accordance  
with ANSI/NFPA No. 409, and in public garages when  
installed in accordance with NFPA No. 88A and NFPA  
No.88B.  
Special attention must be given to any grounding  
information pertaining to this heater.To prevent the risk of  
electrocution, the heater must be securely and adequately  
grounded. This should be accomplished by connecting  
a ground conductor between the service panel and the  
heater.To ensure a proper ground, the grounding means  
must be tested by a qualified electrician.  
Do not insert fingers or foreign objects into heater or its  
air moving device. Do not block or tamper with the heater  
in any manner while in operation, or just after it has been  
turned off, as some parts may be hot enough to cause  
injury.  
If installed in Canada, the installation must conform with  
local building codes, or in the absence of local building  
codes, with CGA-B149.1 “Installation Codes for Natural  
Gas Burning Appliances and Equipment” or CGA-B149.2  
“Installation Codes for Propane Gas Burning Appliances  
and Equipment.These unit heaters have been designed  
and certified to comply with CGA 2.6. Also see sections  
on installation in AIRCRAFT HANGARS and PUBLIC  
GARAGES.  
This heater is intended for general heating applications  
ONLY. It must NOT be used in potentially dangerous  
locations such as flammable, explosive, chemical-laden,  
or wet atmospheres.  
Do not attach ductwork to this product or use it as a  
makeup air heater. Such usage voids the warranty and  
will create unsafe operation.  
Do not alter the unit heater in any  
way or damage to the unit and/or severe personal  
injury or death may occur!  
In cases in which property damage may result from  
malfunction of the heater, a back-up system or  
temperature sensitive alarm should be used.  
Disconnect all power and gas  
supplies before installing or servicing the heater.  
If the power disconnect is out of sight, lock  
it in the open position and tag it to prevent  
unexpected application of power. Failure to do  
so could result in fatal electric shock, or severe  
personal injury.  
The open end of piping systems being  
purged shall not discharge into areas where there  
are sources of ignition or into confined spaces  
UNLESS precautions are taken as follows: (1) by  
ventilation of the space, (2) control of the purging  
rate, (3) elimination of all hazardous conditions. All  
precautions must be taken to perform this operation  
in a safe manner!  
Ensure that all power sources conform  
to the requirements of the unit heater, or damage to  
the unit will result!  
Unless otherwise specified, the following conversions  
may be used for calculating SI unit measurements:  
1 foot = 0.305 m  
1 inch = 25.4 mm  
1 gallon = 3.785 L  
1 pound = 0.453 kg 1 litre/second = CFM x 0.472  
1 psig = 6.894 kPa 1 meter/second = FPM ÷ 196.8  
1 cubic foot = 0.028m3  
Follow installation instructions CAREFULLY to avoid  
creating unsafe conditions. All wiring should be done  
and checked by a qualified electrician, using copper wire  
only. All gas connections should be made and leak-tested  
by a suitably qualified individual, per instructions in this  
manual. Also follow procedures listed on “Gas Equipment  
Start-Up Sheet” located in this manual.  
1000 BTU/cu. ft. = 37.5 MJ/m3  
1000 BTU per hour = 0.293 kW  
1 inch water column = 0.249 kPa  
Use only the fuel for which the heater is designed (see  
rating plate). Using LP gas in a heater that requires  
natural gas, or vice versa, will create risk of gas leaks,  
carbon monoxide poisoning, and explosion.  
3
 
Table 1 - Performance and Dimensional Data - Tubular Propeller Unit Heater  
Unit Size  
100  
125  
150  
175  
200  
250  
300  
350  
400  
PERFORMANCE DATA†  
Input - BTU/Hr.  
(kW)  
Output - BTU/Hr.  
(kW)  
Thermal Efficiency (%)  
Free Air Delivery - CFM  
(cu. m/s)  
Air Temperature Rise - Deg. F  
(Deg. C)  
100,000  
(29.3)  
81,000  
(23.7)  
81  
1,600  
(0.756)  
47  
125,000  
(36.6)  
101,250  
(29.6)  
81  
2,200  
(1.039)  
42  
150,000  
(43.9)  
121,500  
(35.6)  
81  
2,400  
(1.133)  
47  
175,000  
(51.2)  
141,750  
(41.5)  
81  
2,850  
(1.346)  
46  
200,000  
(58.6)  
162,000  
(47.5)  
81  
3,200  
(1.511)  
47  
250,000  
(73.2)  
202,500  
(59.3)  
81  
3,450  
(1.629)  
54  
300,000  
(87.8)  
243,000  
(71.2)  
81  
5,000  
(2.361)  
45  
350,000  
(102.5)  
283,500  
(83.0)  
81  
5,600  
(2.644)  
47  
400,000  
(117.1)  
324,000  
(95.0)  
81  
5,800  
(2.738)  
51  
(26)  
(23)  
(26)  
(26)  
(26)  
(30)  
(24)  
(26)  
(28)  
Full Load Amps at 120V  
5.3  
5.8  
5.8  
8.0  
8.0  
8.0  
11.3  
13.5  
13.5  
MOTOR DATA: Motor HP (Qty.) 1/10  
1/4  
1/4  
1/3  
1/3  
1/3  
(2) 1/4  
(0.19)  
PSC  
1,140  
9.4  
(2) 1/3  
(0.25)  
PSC  
1,140  
11.6  
(2) 1/3  
(0.25)  
PSC  
1,140  
11.6  
Motor kW  
Motor Type  
R.P.M.  
(0.080)  
SP  
1,050  
4.2  
(0.19)  
PSC  
1,140  
4.7  
(0.19)  
PSC  
1,140  
4.7  
(0.25)  
PSC  
1,140  
5.8  
(0.25)  
PSC  
1,140  
5.8  
(0.25)  
PSC  
1,140  
5.8  
Amps @ 115V  
DIMENSIONAL DATA - inches (mm)  
“A” Overall Height to Top of Flue 33-3/4  
(857)  
33-3/4  
(857)  
20-3/4  
(527)  
13-3/8  
(340)  
11  
(279)  
18-5/8  
(473)  
18-3/4  
(476)  
4-3/4  
(121)  
24-1/2  
(622)  
25-1/4  
(641)  
5
33-3/4  
(857)  
20-3/4  
(527)  
13-3/8  
(340)  
11  
(279)  
18-5/8  
(473)  
18-3/4  
(476)  
4-3/4  
(121)  
24-1/2  
(622)  
25-1/4  
(641)  
5
33-3/4  
(857)  
32-3/4  
(831)  
19-3/8  
(492)  
11  
(279)  
30-5/8  
(778)  
30-3/4  
(781)  
4-3/4  
(121)  
24-1/2  
(622)  
37-1/4  
(946)  
5
33-3/4  
(857)  
32-3/4  
(831)  
19-3/8  
(492)  
11  
(279)  
30-5/8  
(778)  
30-3/4  
(781)  
4-3/4  
(121)  
24-1/2  
(622)  
37-1/4  
(946)  
5
33-3/4  
(857)  
32-3/4  
(831)  
19-3/8  
(492)  
11  
(279)  
30-5/8  
(778)  
30-3/4  
(781)  
4-3/4  
(121)  
24-1/2  
(622)  
37-1/4  
(946)  
5
34  
(864)  
50-3/4  
(1289)  
28-3/8  
(721)  
12-1/4  
(311)  
48-5/8  
(1235)  
48-3/4  
(1238)  
5-1/8  
(130)  
24-1/2  
(622)  
55-1/4  
(1403)  
6
34  
(864)  
50-3/4  
(1289)  
28-3/8  
(721)  
12-1/4  
(311)  
48-5/8  
(1235)  
48-3/4  
(1238)  
5-1/8  
(130)  
24-1/2  
(622)  
55-1/4  
(1403)  
6
34  
(864)  
50-3/4  
(1289)  
28-3/8  
(721)  
12-1/4  
(311)  
48-5/8  
(1235)  
48-3/4  
(1238)  
5-1/8  
(130)  
24-1/2  
(622)  
55-1/4  
(1403)  
6
“B” Jacket Width of Unit  
20-3/4  
(527)  
13-3/8  
(340)  
11  
(279)  
18-5/8  
(473)  
18-3/4  
(476)  
4-3/4  
(121)  
24-1/2  
(622)  
25-1/4  
(641)  
5
“C” Width to CL Flue  
“D” Depth to Rear of Housing  
“E” Hanging Distance Width  
“F” Discharge Opening Width  
“G” Depth to CL Flue  
“H” Discharge Opening Height  
LOverall Unit Width  
*Flue Size Diameter - in.  
(Dia.-mm)  
Fan Diameter - in. (Qty.)  
Gas Inlet-Natural Gas (in.)  
Gas Inlet- LP Gas (in.)  
Approximate Unit Weight - lbs.  
(127)  
16  
(127)  
16  
1/2  
1/2  
145  
(127)  
16  
1/2  
1/2  
155  
(127)  
18  
1/2  
1/2  
191  
(127)  
18  
1/2  
1/2  
201  
(127)  
18  
3/4  
1/2 OR 3/4  
211  
(152)  
(2) 16  
3/4  
1/2 OR 3/4  
307  
(152)  
(2) 18  
3/4  
1/2 OR 3/4  
321  
(152)  
(2) 18  
3/4  
1/2 OR 3/4  
335  
1/2  
1/2  
133  
(kg)  
(60)  
173  
(78)  
(66)  
185  
(84)  
(70)  
195  
(88)  
(87)  
241  
(109)  
(91)  
251  
(114)  
(96)  
261  
(118)  
(139)  
367  
(166)  
(145)  
381  
(173)  
(152)  
395  
(179)  
Approximate Ship Weight - lbs.  
(kg)  
* For all installations, the ue collar is included with the unit and should be eld installed per the instructions included with the unit.  
Ratings shown are for unit installations at elevations between 0 and 2,000 ft (0 to 610m). For unit installations in U.S.A. above 2,000 ft. (610m), the unit input must be derated 4% for each 1,000 ft. (305m) above sea level; refer to  
local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54).  
For installations in Canada, any reference to deration at altitudes in excess of 2,000 ft. (610m) are to be ignored. At altitudes of 2,000 ft. to 4,500 ft. (610 to 1372m), the unit must be derated to 90% of the normal altitude rating,  
and be so marked in accordance with the ETL certication.  
1-3/8"  
(35)  
(Hanging)  
32-1/2"  
(826)  
E
L
D
(Hanging)  
11-5/8"  
(295)  
(Hanging)  
Flue  
*
G
B
C
H
A
(Discharge  
Opening)  
33"  
Electrical Control Panel  
1" (25)  
F
Gas Valve  
(Discharge Opening)  
Rear View  
Side View  
Front View  
D4617  
DIMENSIONS .XXX STANDARD UNITS  
DIMENSIONS IN PARENTHESIS (XXX) MILLIMETERS  
Figure 2 - Dimensional Drawing – Tubular Propeller Unit Heater  
4
 
INSTALLATION  
In Canada, installation must be in accordance to the  
latest edition of CGA B149 “Installation Codes for Gas  
Burning Appliances and Equipment.”  
Do not install unit heaters in  
corrosive or flammable atmospheres! Premature  
failure of, or severe damage to the unit will  
result!  
AIR DISTRIBUTION: Direct air towards areas of  
maximum heat loss. When multiple heaters are involved,  
circulation of air around the perimeter is recommended  
where heated air flows along exposed walls. Satisfactory  
results can also be obtained where multiple heaters are  
located toward the center of the area with heated air  
directed toward the outside walls. Be careful to avoid all  
obstacles and obstructions which could impede the warm  
air distribution patterns.  
Avoid locations where extreme  
drafts can affect burner operation. Unit heaters  
must not be installed in locations where air for  
combustion would contain chlorinated, halo-  
genated or acidic vapors. If located in such an  
environment, premature failure of the unit will  
occur!  
Since the unit is equipped with an automatic gas ignition  
system, the unit heater must be installed such that the  
gas ignition control system is not directly exposed to  
water spray, rain or dripping water.  
Unit heaters should not be installed to maintain low  
temperatures and/or freeze protection of buildings.  
A minimum of 50°F (10°C) thermostat setting must  
be maintained. If unit heaters are operated to maintain  
lower than 50°F (10°C), hot flue gases are cooled  
inside the heat exchanger to a point where water  
vapor (a flue gas by-product) condenses onto the heat  
exchanger walls. The result is a mildly corrosive acid that  
prematurely corrodes the aluminized heat exchanger and  
can actually drip water down from the unit heater onto  
floor surface. Additional unit heaters should be installed  
if a minimum 50°F (10°C) thermostat setting cannot be  
maintained.  
NOTICE: Location of unit heaters is related directly to  
the selection of sizes. Basic rules are as follows:  
MOUNTING HEIGHT: Unit Heaters equipped with  
standard fan guards must be installed at a minimum of  
8 feet (2.4m) above the floor, measured to the bottom of  
the unit. At heights above 8 feet (2.4m), less efficient air  
distribution will result. If a unit is to be mounted below  
8 feet (2.4m) from the floor, an OSHA approved fan  
guard is required on the unit.  
AIR FOR COMBUSTION: The unit heater shall be  
installed in a location in which the facilities for  
ventilation permit satisfactory combustion of gas,  
proper venting, and the maintenance of ambient  
air at safe limits under normal conditions of use.  
The unit heater shall be located in such a manner as  
not to interfere with proper circulation of air within the  
confined space. When buildings are so tight that normal  
infiltration does not meet air requirements, outside air  
shall be introduced per Sections 1.3.4.2 and 1.3.4.3 of  
ANSI Z223.1 for combustion requirements. A permanent  
opening or openings having a total free area of not less  
than one square inch per 5,000 BTU/Hr (1.5 kW) of total  
input rating of all appliances within the space shall be  
provided.  
AIRCRAFT HANGARS: Unit Heaters must be installed  
in aircraft hangars as follows: In aircraft hangars, unit  
heaters must be at least 10 feet (3.0m) above the upper  
surface of wings or engine enclosures of the highest  
aircraft to be stored in the hangar, and 8 feet (2.4m)  
above the floor in shops, offices and other sections of  
the hangar where aircraft are not stored or housed.  
Refer to current ANSI/NFPA No. 409, Aircraft Hangars. In  
Canada, installation is suitable in aircraft hangars when  
acceptable to the enforcing authorities.  
PUBLIC GARAGES: In repair garages, unit heaters must  
be located at least 8 feet (2.4m) above the floor. Refer to  
the latest edition of NFPA 88B, Repair Garages.  
NOTICE: Unit Heater sizing should be based on heat  
loss calculations where the unit heater output equals  
or exceeds heat loss.  
In parking structures, unit heaters must be installed so  
that the burner flames are located a minimum of 18 in.  
(457mm) above the floor or protected by a partition not  
less than 18 in. (457mm) high. However, any unit heater  
mounted in a parking structure less than 8 ft.(2.4m) above  
the floor must be equipped with an OSHA approved fan  
guard. Refer to the latest edition of NFPA 88A, Parking  
structures.  
5
 
INSTALLATION (continued)  
CLEARANCES: Each Gas Unit Heater shall be Figure 3A  
located with respect to building construction and other  
equipment so as to permit access to the Unit Heater.  
Clearance between vertical walls and the vertical  
sides of the Unit Heater shall be no less than 6 inches  
(152mm). However, to ensure access to the control box,  
a minimum of 18" (457mm) is required for the control  
box side. A minimum clearance of 6 inches (152mm)  
must be maintained between the top of the Unit Heater  
and the ceiling. The bottom of the Unit Heater must be  
no less than 12 inches (305mm) from any combustible.  
The distance between the flue collector and any  
combustible must be no less than 6 inches (152mm).  
Also see AIR FOR COMBUSTION and VENTING  
sections.  
NOTICE: Increasing the clearance distances may  
be necessary if there is a possibility of distortion or  
discoloration of adjacent materials.  
Make certain that the lifting  
methods used to lift the heater and the method  
of suspension used in the field installation of the  
heater are capable of uniformly supporting the  
weight of the heater at all times. Failure to heed  
this warning may result in property damage or  
personal injury!  
Figure 3B - Heater Mounting*  
Make sure that the structure  
to which the unit heater is to be mounted is  
capable of safely supporting its weight. Under  
no circumstances must the gas lines, the venting  
system or the electrical conduit be used to  
support the heater; or should any other objects  
(i.e. ladder, person) lean against the heater gas  
lines, venting system or the electrical conduit  
for support. Failure to heed these warnings may  
result in property damage, personal injury, or  
death.  
*All hanging hardware and wood is not included with the unit (To  
be field supplied).  
Figure 3C  
Unit Heaters must be hung level  
from side to side and from front to back, see Figure  
3A, 3B and 3C. Failure to do so will result in poor  
performance and/or premature failure of the unit.  
Ensure that all hardware used in  
the suspension of each unit heater is more than  
adequate for the job. Failure to do so may result  
in extensive property damage, severe personal  
injury, or death!  
Refer to Figures 3A, 3B and 3C for suspension of units.  
6
 
GAS PIPING  
To avoid damage or possible personal injury, do not connect gas piping to this unit  
until a supply line pressure/leak test has been completed. Connecting the unit before completing the  
pressure/leak test may damage the unit gas valve and result in a fire hazard.  
Do not rely on a shut-off valve to isolate the unit while conducting gas pressure/leak  
tests.These valves may not be completely shut off, exposing the gas valve to excessive pressure and  
damage.  
PIPE SIZING  
NOTICE: If more than one unit heater is to be served  
To provide adequate gas pressure to the gas unit heater, by the same piping arrangement, the total cu. ft./hr.  
size the gas piping as follows:  
input and length of pipe must be considered.  
1. Find the cu. ft./hr. by using the following formula:  
NOTICE: If the gas unit heater is to be fired with LP  
gas, consult your local LP gas dealer for pipe size  
information.  
Input BTU/Hr.  
Cu. ft./hr. =  
1000  
2. Refer to Table 3. Match “Length of Pipe in Feet”  
with appropriate “Gas Input - Cu. Ft./Hr.gure. This  
figure can then be matched to the pipe size at the  
top of the column.  
NOTICE: HEATER INSTALLATION FOR USE WITH  
PROPANE (BOTTLED) GAS MUST BE MADE BY  
A QUALIFIED L.P. GAS DEALER OR INSTALLER.  
HE/SHE WILL INSURE THAT PROPER JOINT  
COMPOUNDS ARE USED FOR MAKING PIPE  
CONNECTIONS; THAT AIR IS PURGED FROM  
LINES; THAT A THOROUGH TEST IS MADE FOR  
LEAKS BEFORE OPERATING THE HEATER; AND  
THAT IT IS PROPERLY CONNECTED TO THE  
PROPANE GAS SUPPLY SYSTEM.  
Example:  
It is determined that a 67 foot (20.4m) run of gas  
pipe is required to connect a 200 MBTU gas unit  
heater to a 1,000 BTU/cu ft. (0.29kW) natural gas  
supply.  
200,000 BTU/Hr  
1,000 BTU/cu. ft.  
= 200 Cu. ft./hr.  
Using Table 3, a 1 inch pipe is needed.  
Before any connection is made to the existing line  
supplying other gas appliances, contact the local gas  
company to make sure that the existing line is of adequate  
size to handle the combined load.  
NOTE: See General Safety Information section for  
English/Metric unit conversion factors.  
Table 3 - Gas Pipe Size  
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour (Cubic Meters per Hour) for Gas Pressures of 0.5 psig (3.5 kPa) or Less,  
and a Pressure Drop of 0.5 Inch Water Column (124.4 Pa)  
(Based on a 0.60 Specific Gravity Gas)  
Nominal  
Iron  
Internal  
Dia.  
Length of Pipe, Feet (meters)  
Pipe Size  
in.  
10  
20  
30  
(9.1)  
97  
40  
(12.2) (15.2) (18.3) (21.3) (24.4) (27.4) (30.5) (38.1) (45.7) (53.3) (61.0)  
82 73 66 61 57 53 50 44 40 37 35  
50  
60  
70  
80  
90  
100  
125  
150  
175  
200  
in.  
0.622  
(3.0)  
175  
(6.1)  
120  
1/2  
(4.96) (3.40) (2.75) (2.32) (2.07) (1.87) (1.73) (1.61) (1.50) (1.42) (1.25) (1.13) (1.05) (0.99)  
360 250 200 170 151 138 125 118 110 103 93 84 77 72  
(10.2) (7.08) (5.66) (4.81) (4.28) (3.91) (3.54) (3.34) (3.11) (2.92) (2.63) (2.38) (2.18) (2.04)  
680 465 375 320 285 260 240 220 205 195 175 160 145 135  
(19.3) (13.2) (10.6) (9.06) (8.07) (7.36) (6.80) (6.23) (5.80) (5.52) (4.96) (4.53) (4.11) (3.82)  
1400 950 770 660 580 530 490 460 430 400 360 325 300 280  
(39.6) (26.9) (21.8) (18.7) (16.4) (15.0) (13.9) (13.0) (12.2) (11.3) (10.2) (9.20) (8.50) (7.93)  
2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430  
(59.5) (41.3) (33.4) (28.0) (25.5) (22.9) (21.2) (19.5) (18.4) (17.6) (15.6) (14.2) (13.0) (12.2)  
3950 2750 2200 1900 1680 1520 1400 1300 1220 1150 1020 950 850 800  
(112) (77.9) (62.3) (53.8) (47.6) (43.0) (39.6) (36.8) (34.5) (32.6) (28.9) (26.9) (24.1) (22.7)  
3/4  
1
0.824  
1.049  
1.380  
1.610  
2.067  
2.469  
1 1/4  
1 1/2  
2
2 1/2  
3
6300  
(178)  
4350  
3520  
3000  
2650  
2400  
2250  
2050  
1950  
1850  
1650  
1500  
1370  
1280  
(123) (99.7) (85.0) (75.0) (68.0) (63.7) (58.0) (55.2) (52.4) (46.7) (42.5) (38.8) (36.2)  
3.068 11000 7700  
(311) (218)  
4.026 23000 15800 12800 10900 9700  
(651) (447) (362) (309) (275)  
6250  
(177)  
5300  
(150)  
4750  
(135)  
4300  
(122)  
8800  
(249)  
3900  
(110)  
8100  
(229)  
3700  
(105) (97.7) (92.0) (83.5) (75.0) (69.4) (64.6)  
3450  
3250  
2950  
2650  
2450  
2280  
4
7500  
(212)  
7200  
(204)  
6700  
(190)  
6000  
(170)  
5500  
(156)  
5000  
(142)  
4600  
(130)  
1. Determine the required Cu. Ft./Hr. by dividing the input by 1000. For SI/Metric measurements: Convert BTU/Hr. to kilowatts. Multiply the units  
inputs (kW) by 0.0965 to determine Cu. Meters./Hr. 2. FOR NATURAL GAS: Select pipe size directly from the table. 3. FOR PROPANE GAS:  
Multiply the Cu. Ft./Hr. value by 0.633; then, use the table. 4. Refer to the metric conversion factors listed in the General Safety section for SI Unit  
measurement conversions.  
7
 
PIPE INSTALLATION  
1. Install the gas piping in accordance with applicable Figure 4 - Pipe Installation, Standard Controls  
local codes.  
2. Check gas supply pressure. Each unit heater must  
be connected to a manifold pressure and a gas  
supply capable of supplying its full rated capacity  
as specified in Table 4. A field LP tank regulator  
must be used to limit the supply pressure to a  
maximum of 14 in. W.C. (3.5 kPa). All piping should  
be sized in accordance with the latest edition of  
ANSI Standard Z223.1, National Fuel Gas Code;  
in Canada, according to CGA B149. See Tables  
1 & 3 for correct gas piping size. If gas pressure  
is excessive on natural gas applications, install a  
pressure regulating valve in the line upstream from  
the main shutoff valve.  
3. Adequately support the piping to prevent strain on  
the gas manifold and controls.  
4. To prevent the mixing of moisture with gas, run the  
take-off piping from the top, or side, of the main.  
5. Standard Unit Heaters, optional two-stage units are  
supplied with a combination valve which includes:  
a. Manual "A" valve  
Never use an open flame to detect  
gas leaks. Explosive conditions may exist which  
may result in personal injury or death!  
b. Manual "B" valve  
c. Solenoid valve  
d. Pressure regulator  
The appliance and its individual shutoff valve must be  
disconnected from the gas supply piping system during  
Pipe directly into the combination valve (see Figure any pressure testing of that system in excess of 1/2 psig  
4).  
(3.5 kPa).  
6. Gas valve has a pressure test post requiring a  
3/32" hex head wrench to read gas supply and The appliance must be isolated from the gas supply  
manifold pressures. Open 1/4 turn counterclockwise piping system by closing its individual manual shutoff  
to read, turn clockwise to close and reseat. A 5/16" valve during any pressure testing of the gas supply  
ID hose fits the pressure post.  
piping system at test pressures equal to or less than  
7. Provide a drip leg in the gas piping near the gas 1/2 psig (3.5 kPa).  
unit heater. A ground joint union and a manual gas  
shutoff valve should be installed ahead of the unit  
heater controls to permit servicing. The manual  
shutoff valve must be located external to the jacket  
(See Figure 4).  
Table 4 - Gas Piping Requirements  
SINGLE STAGE GAS PIPING REQUIREMENTS*  
GasType  
Natural Gas  
Propane (LP) Gas  
Manifold  
Pressure  
3.5 in. W.C.  
(0.9 kPa)  
10.0 in. W.C.  
(2.5 kPa)  
8. Make certain that all connections have been  
adequately doped and tightened.  
14.0 in. W.C. Max.  
(3.5 kPa)  
14.0 in. W.C. Max.  
(3.5 kPa)  
Supply Inlet  
Pressure  
Do not over tighten the inlet gas  
piping into the valve. This may cause stresses that  
will crack the valve!  
5.0 in. W.C. Min.  
(1.2 kPa)  
11.0 in W.C. Min.  
(2.7 kPa)  
*For single stage application only at normal altitudes.  
NOTICE: Use pipe joint sealant resistant to the  
action of liquefied petroleum gases regardless of  
gas conducted.  
Check all pipe joints for leakage  
using a soap solution or other approved method.  
Never use an open flame or severe personal  
injury or death may occur!  
8
 
ELECTRICAL CONNECTIONS  
Figure 5a -  
Low-voltage T  
Thermostat Wiring  
Single Stage  
HAZARDOUS VOLTAGE!  
DISCONNECT ALL ELECTRIC  
POWER INCLUDING REMOTE  
DISCONNECTS BEFORE  
SERVICING. Failure to  
Figure 5b -  
Low-voltage  
Thermostat Wiring  
Two Stage  
disconnect power before  
servicing can cause severe  
personal injury or death.  
Standard units are shipped for use on 115 volt, 60 hertz,  
single phase electric power. The motor name-plate and  
electrical rating of the transformer should be checked  
before energizing the unit heater electrical system. All  
external wiring must conform to the latest edition of  
ANSI/NFPA No. 70, United States National Electrical  
Code, and applicable local codes; in Canada, to the  
Canadian Electrical Code, Part 1, CSA Standard C22.1.  
Honeywell  
T834H-1009  
or  
T834H-1017  
Thermostat  
Figure 5c -  
T834H-1009 or  
T834H-1017  
W
R
G
Thermostat Wiring  
R
G
W1 W2  
D6922B  
Do not use any tools (i.e. screwdriver,  
pliers, etc.) across terminals to check for power. Use  
a voltmeter.  
THERMOSTAT HEAT ANTICIPATOR ADJUSTMENTS:  
The initial heat anticipator setpoint should equal the  
thermostat's current amperage draw when the unit is  
firing. This setpoint should be measured for the best  
results. Use the recommended ranges for a guide. If  
further information is needed, consult your thermostat  
manufacturer's instructions.  
It is recommended that the electrical power supply to  
each unit heater be provided by a separate, fused, and  
permanently live electrical circuit. A disconnect switch of  
suitable electrical rating should be located as close to  
the gas valve and controls as possible. Each unit heater  
must be electrically grounded in accordance with the  
latest edition of the United States National Electrical  
Code, ANSI/NFPA No. 70, or CSA Standard C22.1. Refer  
to Figures 5a, 5b, 5c, 5d and 5e.  
Recommended heat anticipator settings:  
Unit Size:  
30 thru 200  
250 thru 400  
For Tubular Units:  
0.35 Amps  
0.65 Amps  
THERMOSTAT WIRING AND LOCATION:  
NOTICE: The start-up fan delay should not exceed  
30 seconds from a cold start.  
NOTICE: The thermostat must be mounted on a  
vertical, vibration-free surface, free from air currents,  
and in accordance with the furnished instructions.  
IMPORTANT: For all wiring connections, refer to the  
wiring diagram shipped with your unit (either affixed  
to the side jacket or enclosed in the installation  
instructions envelope). Should any original wire  
supplied with the heater have to be replaced, it  
must be replaced with wiring material having a  
temperature rating of at least 105° C.  
Mount the thermostat approximately 5 feet (1.5m) above  
the floor, in an area where it will be exposed to a free  
circulation of average temperature air. Always refer to  
the thermostat instructions, as well as our unit wiring  
diagram, and wire accordingly. Avoid mounting the  
thermostat in the following locations:  
1. Cold Areas - Outside walls or areas where drafts  
may affect the operation of the control.  
2. Hot Areas - Areas where the sun's rays, radiation,  
or warm air currents may affect the operation of  
the control.  
Should any high limit wires have to be replaced,  
they must be replaced with wiring material having a  
temperature rating of 200° C minimum.  
3. Dead Areas - Areas where the air cannot circulate  
freely, such as behind doors or in corners.  
9